Fluke 1507 Insulation Tester
When you need a low cost solution to general purpose insulation testing look no further than the Fluke 1507 Insulation Tester. The Fluke 1507 Insulation Tester is compact, rugged, reliable, and easy to use. With it’s multiple test voltages, it is ideal for many troubleshooting, commissioning, and preventative maintenance applications.
Additional features, like the remote probe saves both time and money when performing tests.
Fluke 1507 Technical Specifications
AC/DC Voltage Measurements | |
---|---|
Range | 600V |
Resolution | 0.1V |
Accuracy | 50Hz to 400Hz ± (% of Rdg Digits) ± (2% 3) |
Input Impedance | 3MΩ (nominal) < 100pF |
Common Mode Rejection Ratio (1kΩ unbalanced) | >60dB at DC, 50 or 60Hz |
Overload Protection | 600V rms or DC |
Earth Bond Resistance Measurements | |
Range/Resolution | 20Ω: 0.01Ω 200Ω: 0.1Ω 2000Ω: 1.0Ω 20kΩ: 0.01kΩ |
Accuracy | ± (1.5% 3) |
Overload Protection | 2V rms or DC |
Open Circuit Test Voltage | >4V, <8V |
Short Circuit Current | >200mA |
Insulation Specifications | |
Measurement Range | 1507: 0.01MΩ to 10GΩ |
Test Voltage | 50V, 100V, 250V, 500V, 1000V |
Test Voltage Accuracy | 20%, -0% |
Short Circuit Current | 1mA nominal |
Auto Discharge | Discharge time < 0.5 seconds for C = 1μF or less |
Live Circuit Indicator | Inhibit test if terminal voltage >30V prior to initialisation of test |
Maximum Capacitive Load | Operable with up to 1μF load |
Measurement Accuracy | 50V: ±(3% 5) 100V: ±(3% 5) 250V: ±(1.5% 5) 500V: ±(1.5% 5) 1000V: ±(1.5% 5) to 2000MΩ, ±(10% 3) above 2000MΩ |
General Specifications | |
Maximum Voltage Applied to Any Terminal | 600V AC rms or DC |
Storage Temperature | -40 to 60°C (-40 to 140°F) |
Operating Temperature | -20 to 55°C (-4 to 131°F) |
Temperature Coefficient | 0.05x (specified accuracy) per °C for temperatures < 18°C or > 28°C (<64°F or >82°F) |
Relative Humidity | 0 to 95% @ 10°C to 30°C (50°F to 86°F) 0 to 75% @ 30°C to 40°C (86°F to 104°F) 0 to 40% @ 40°C to 55°C (104°F to 131°F) |
Vibration | Random, 2g, 5-500Hz per MIL-PRF-28800F, class 2 instrument |
Shock | 1m drop per IEC 61010-1 2nd Edition (1m drop test, six sides, oak floor) |
Electromagnetic Compatibility | In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1: 1997) |
Safety | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600V (CAT IV) |
Certifications | CSA per standard CSA/CAN C22.2 No 61010-1-04; TUV per standard IEC/EN 61010-1 2nd Edition |
Batteries | Four x AA batteries (NEDA 15A or IEC LR6) |
Battery Life | Insulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000V into 1MΩ with a duty cycle of 5 seconds on and 25 seconds off. Resistance measurements: Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1Ω with a duty cycle of 5 seconds on and 25 seconds off |
Size | 5.0cm H x 10.0cm W x 20.3cm L (1.97″ x 3.94″ x 8.00″) |
Weight | 550g (1.2lb) |
IP Rating | IP40 |
Altitude | Operating: 2000m CAT IV 600V, 3000m CAT III 600V Non-Operating (Storage): 12000m |
Overrange Capability | 110% of range |