01785 600 691enquiries@thecalcentre.co.uk

Save

29%

On RRP

Fluke 1507 Insulation Tester

£449.43 Inc VAT: £539.32

    2 in stock (can be backordered)

    Calibration Certificate

    Add a 12 month Calibration Certificate

    Description

    Fluke 1507 Insulation Tester

    When you need a low cost solution to general purpose insulation testing look no further than the Fluke 1507 Insulation Tester. The Fluke 1507 Insulation Tester is compact, rugged, reliable, and easy to use. With it’s multiple test voltages, it is ideal for many troubleshooting, commissioning, and preventative maintenance applications.

    Additional features, like the remote probe saves both time and money when performing tests.

    Fluke 1507 Technical Specifications

    AC/DC Voltage Measurements
    Range600V
    Resolution0.1V
    Accuracy50Hz to 400Hz ± (% of Rdg Digits) ± (2% 3)
    Input Impedance3MΩ (nominal) < 100pF
    Common Mode Rejection Ratio (1kΩ unbalanced)>60dB at DC, 50 or 60Hz
    Overload Protection600V rms or DC
    Earth Bond Resistance Measurements
    Range/Resolution20Ω: 0.01Ω
    200Ω: 0.1Ω
    2000Ω: 1.0Ω
    20kΩ: 0.01kΩ
    Accuracy± (1.5% 3)
    Overload Protection2V rms or DC
    Open Circuit Test Voltage>4V, <8V
    Short Circuit Current>200mA
    Insulation Specifications
    Measurement Range1507: 0.01MΩ to 10GΩ
    Test Voltage50V, 100V, 250V, 500V, 1000V
    Test Voltage Accuracy 20%, -0%
    Short Circuit Current1mA nominal
    Auto DischargeDischarge time < 0.5 seconds for C = 1μF or less
    Live Circuit IndicatorInhibit test if terminal voltage >30V prior to initialisation of test
    Maximum Capacitive LoadOperable with up to 1μF load
    Measurement Accuracy50V: ±(3% 5)
    100V: ±(3% 5)
    250V: ±(1.5% 5)
    500V: ±(1.5% 5)
    1000V: ±(1.5% 5) to 2000MΩ, ±(10% 3) above 2000MΩ
    General Specifications
    Maximum Voltage Applied to Any Terminal600V AC rms or DC
    Storage Temperature-40 to 60°C (-40 to 140°F)
    Operating Temperature-20 to 55°C (-4 to 131°F)
    Temperature Coefficient0.05x (specified accuracy) per °C for temperatures < 18°C or > 28°C (<64°F or >82°F)
    Relative Humidity0 to 95% @ 10°C to 30°C (50°F to 86°F)
    0 to 75% @ 30°C to 40°C (86°F to 104°F)
    0 to 40% @ 40°C to 55°C (104°F to 131°F)
    VibrationRandom, 2g, 5-500Hz per MIL-PRF-28800F, class 2 instrument
    Shock1m drop per IEC 61010-1 2nd Edition (1m drop test, six sides, oak floor)
    Electromagnetic CompatibilityIn an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1: 1997)
    SafetyComplies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600V (CAT IV)
    CertificationsCSA per standard CSA/CAN C22.2 No 61010-1-04; TUV per standard IEC/EN 61010-1 2nd Edition
    BatteriesFour x AA batteries (NEDA 15A or IEC LR6)
    Battery LifeInsulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000V into 1MΩ with a duty cycle of 5 seconds on and 25 seconds off.
    Resistance measurements: Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1Ω with a duty cycle of 5 seconds on and 25 seconds off
    Size5.0cm H x 10.0cm W x 20.3cm L (1.97″ x 3.94″ x 8.00″)
    Weight550g (1.2lb)
    IP RatingIP40
    AltitudeOperating: 2000m CAT IV 600V, 3000m CAT III 600V
    Non-Operating (Storage): 12000m
    Overrange Capability110% of range
    • Insulation test range from 0.01MΩ to 10GΩ
    • Test voltages of 50V, 100V, 250V, 500V and 1000V
    • Automatic calculation of polarisation index and dielectric absorption ratio
    • Compare (PASS/FAIL) function for repetitive tests
    • Includes remote probe for hard-to-reach testing applications
    • Live circuit detection – prevents insulation test if voltages above 30V are detected
    • Auto discharge of capacitive voltage
    • AC/DC voltage measurements from 0.1V to 600V
    • 200mA continuity test
    • Resistance measurements from 0.01Ω to 20kΩ
    • Auto power off switches the meter off when left idle
    • Large-size backlit LCD display
    • CAT IV 600V overvoltage rating
    • Powered by 4x AA alkaline batteries
    • Fluke 1507 Insulation Tester
    • Remote Probe
    • Test Leads
    • Test Probes
    • Alligator Clips
    • User Documentation